Winterizing Fire Sprinkler Systems
Joe Stauffer on 09/24/2024

Winterizing Fire Sprinkler Systems

Cold weather and freezing temperatures are on the way! Remember these key facts from NFPA 25. The building owner is responsible for keeping their system dry!

J Joe Stauffer
Service/Inspection Bulletin - Tyco DPV-1 clogged internal alarm line port
Joe Stauffer on 06/07/2023

Service/Inspection Bulletin - Tyco DPV-1 clogged internal alarm line port

If you run into an issue where a Tyco DPV-1 trips and does not send an alarm, check the 3/4" alarm line coming out the back of the DPV-1 by breaking the unions and removing the nipple. There is (2) small holes machined into the housing of the DPV-1 port that easily get clogged and will not allow water to flow to the pressure switch, thus not sending a signal when the valve trips. Clean & flush the ports, problem solved.

J Joe Stauffer
Technical Support
Keith Kingswell on 05/02/2023

Technical Support

If you need technical support, use the following contact information.