CFP Driver Scores Updates - November 2024
Attention CFP Drivers:

Attention CFP Drivers:
ATTENTION ALL CFP DRIVERS:
THIS... is exactly the kind of teamwork we should celebrate.
Cold weather and freezing temperatures are on the way! Remember these key facts from NFPA 25. The building owner is responsible for keeping their system dry!
Watch your speed...
Hello Everyone,
NFPA 13: Testing.
Jon Kettoman and Lynn Rosario (Lancaster inspection department) recently passed NICET ITWBS level 1 exam!
Congratulations Jared Goldy !!!
If you run into an issue where a Tyco DPV-1 trips and does not send an alarm, check the 3/4" alarm line coming out the back of the DPV-1 by breaking the unions and removing the nipple. There is (2) small holes machined into the housing of the DPV-1 port that easily get clogged and will not allow water to flow to the pressure switch, thus not sending a signal when the valve trips. Clean & flush the ports, problem solved.

Flowing 3500 GPM Diesel fire pump! Bayer Healthcare 2022 fire pump test

heads up?
If you need technical support, use the following contact information.
Why Test?
Our goal at Dyne Fire Protection Labs is to make testing Quick, Easy, and Accurate. With just a few clicks or a phone call, we put a foam sampling kit right in your hands. Our firefighting foam/antifreeze kits include plastic bottles and caps, a pen for filling out the form, an etching marker to write on the sample bottles, a return shipping label, and paperwork to submit with the sample(s). We also have a fillable PDF of this same form, which allows you to save the logistics, therefore saving time.
Things to Consider When Foam Sampling
SET UP: